Conductor: Solid or Stranded tinned, annealed copper per ASTM B33.
Sizes: #24 AWG - #4/0 AWG.
Insulation: Extruded FEP fluoropolymer jacket. This product is available in
a wide range of colors.
Applications: Used for wiring of electric heaters, appliances, thermocouples, gas
igniters, electrical and electronic components, and other products up to
200° C.
Provides excellent resistance to gasoline, oil, moisture, and acids.
Approvals: UL/CSA Approved Lead Wire
UL Style as listed. This product is also CSA recognized as appliance
wire.
AWG
Stranding
Insulation
Thickness
Overall
Diameter
Amps
Weight
Lbs/Mft
Temp
Rating
24
Solid
0.020
0.065
14
4
200 °C
22
Solid
0.020
0.070
19
5
200 °C
20
Solid
0.020
0.080
26
7
200 °C
18
7/.0152
0.020
0.090
32
10
200 °C
16
7/.0192
0.020
0.100
35
13
200 °C
14
7/.0242
0.020
0.110
45
17
200 °C
12
19/.0179
0.020
0.130
55
25
200 °C
10
37/.0159
0.020
0.160
75
35
200 °C
8
54/.0179
0.030
0.230
100
70
200 °C
6
84/.0179
0.030
0.270
135
105
200 °C
4
133/.0177
0.030
0.325
180
160
200 °C
2
133/.0223
0.030
0.395
240
235
200 °C
1
259/.0177
0.045
0.470
280
320
200 °C
1/0
259/.0202
0.045
0.515
325
400
200 °C
2/0
259/.0229
0.045
0.570
370
495
200 °C
4/0
259/.0286
0.045
0.690
510
730
200 °C
*Dimensions and weights shown
are nominal, subject to standard industry tolerances.