Silicone
Rubber Glass Braid Conductors
With an
Overall Silicone Rubber Jacket
600 volts,
200ºC, 16 Awg - 10 Awg
Description:
Conductor:
Stranded tinned,
annealed copper per ASTM B33.
Sizes: 16 Awg - 10 Awg
Insulation: Silicone rubber
with a fiberglass braid over the insulation.
Cable: The conductors are
cabled with a left hand lay and bound with a polyester tape. An overall
silicone rubber jacket covers the core.
Applications: Used for equipment wiring, as well as
signal and control circuits. Ideal in locations where high temperature or
hazardous conditions exist requiring heat resistance at 600 volts.
16
Awg (7/.0192) .030 Insulation
Cond
Silicone
Jacket
Cable
OD
Weight
Lbs / Mft
Temperature
Rating
2
.045
0.355
60
200ºC
3
.045
0.375
75
200ºC
4
.045
0.410
95
200ºC
5
.045
0.455
110
200ºC
7
.045
0.485
145
200ºC
9
.060
0.595
200
200ºC
12
.060
0.665
255
200ºC
19
.060
0.775
375
200ºC
24
.080
0.945
500
200ºC
37
.080
1.075
720
200ºC
14 Awg
(7/.0242) .030 Insulation
Cond
Silicone
Jacket
Cable
OD
Weight
Lbs / Mft
Temperature
Rating
2
.045
0.385
52
200ºC
3
.045
0.405
96
200ºC
4
.045
0.445
120
200ºC
5
.045
0.485
144
200ºC
7
.060
0.560
208
200ºC
9
.060
0.650
261
200ºC
12
.060
0.725
336
200ºC
19
.080
0.890
534
200ºC
24
.080
1.035
641
200ºC
12 Awg
(19/.0179) .030 Insulation
Cond
Silicone
Jacket
Cable
OD
Weight
Lbs / Mft
Temperature
Rating
2
.045
0.415
96
200ºC
3
.045
0.440
124
200ºC
4
.045
0.480
159
200ºC
5
.060
0.560
195
200ºC
7
.060
0.605
277
200ºC
9
.060
0.705
352
200ºC
12
.060
0.790
457
200ºC
19
.080
0.965
725
200ºC
24
.080
1.125
908
200ºC
10 Awg
(19/.0234) .045 Insulation
Cond
Silicone
Jacket
Cable
OD
Weight
Lbs / Mft
Temperature
Rating
2
.060
0.565
170
200ºC
3
.060
0.600
233
200ºC
4
.060
0.655
296
200ºC
5
.060
0.720
362
200ºC
7
.060
0.785
485
200ºC
9
.080
0.960
650
200ºC
12
.080
1.075
842
200ºC
Dimensions and weights are nominal, subject
to standard industry tolerances.
Dimensions and weights for other cable configurations are available upon
request.